UL전선 규격별 전류 허용치허용전류표 2020. 8. 28. 09:08
UL전선 규격별 전류 허용치
Type
(구분Conductor
(도체)
Insulation
(절연체)
Max.Conductor
Resistancemin.lnsulation
ResistanceDielectric
WithstandingCurrent
(carryingUnit
LengthAWG Size
(규격)
Number& dia of conductor
pcs/mm
(구성)
No.overall
Diameter mm
(외경)
Norminal
thickness
mm
(두께)Norminal
Diameter
mm
(외경)DC 20˚C
Ω/㎞
(최대 도체저항)
DC 15.6˚C
MΩ/㎞
(최소
절연저항)
Voltage
AC V/min
(내전압)
capacity)
Amp
(허용전류)
m
(feet)
(조장)
Stranded 30 7/0.102 0.31 0.4 1.15 376.96 15 2000 2.3 610 28 7/0.127 0.38 0.4 1.25 237.38 3 -2000 (연선) 26 7/0.160 0.48 0.4 1.35 148.94 4 24 11/0.160 0.61 0.4 1.45 93.25 5.3 22 17/0.160 0.76 0.4 1.6 55 7.2 20 21/0.180 0.95 0.4 1.8 34.6 9.4 18 34/0.180 1.21 0.4 2 21.8 12.5 16 26/0.26 1.55 0.4 2.4 13.7 15.9 Solid 30 1/0.26 0.26 0.4 1.1 361.13 15 2000 2.3 610 28 1/0.32 0.32 0.4 1.15 227.39 3 -2000 (단심) 26 1/0.404 0.4 0.4 1.2 142.79 4 24 1/0.511 0.51 0.4 1.35 89.39 5.3 22 1/0.643 0.64 0.4 1.45 54.3 7.2 20 1/0.813 0.81 0.4 1.65 33.9 9.4 18 1/1.024 1.02 0.4 1.85 21.4 12.5 16 1/1.29 1.29 0.4 2.1 12.5 15.9 TA-SC 28 7/0.127 0.38 0.4 1.25 222.33 15 2000 3 610 (Hiwrap) 26 7/0.160 0.48 0.4 1.35 138.88 4 -2000 24 7/0.203 0.61 0.4 1.45 85.41 5.3 22 7/0.26 0.79 0.4 1.6 54.44 7.2 '허용전류표' 카테고리의 다른 글